LMZC(2,3)-10 O'tkazuvchi yadrali qoplamali rezinaviy tok transformatori, 10 kV, yopiq tur, gaz izolyatsiyali uloqtirgichlar uchun

Nominal birinchi 50-600 A, ikkinchi 5 A yoki 1 A, o'lchash sinfi 0.2s/0.2/0.5, himoya sinfi 10P15/10P10/10P5, ikkita chulg'am

So'rov yuborish
  • Umumiy ko'rinish

Umumiy ko'rinish

LMZC(2,3)-10 O'tkazuvchi yadrali qoplangan rezinadan yasalgan tok Transformator 10 kV yopiq tur, gaz bilan izolyatsiyalangan qo'shimcha o'rnatishlar uchun

LMZC(2,3)-10 O'tkazuvchi yadrali qoplangan rezinadan yasalgan tok transformatori — 10 kV gaz bilan izolyatsiyalangan qo'shimcha o'rnatishlar va shunga o'xshash tarqatish uskunalari uchun mo'ljallangan yopiq, qoplangan rezinadan yasalgan o'lchov transformatoridir. Ushbu seriyaga LMZC3-10 va LMZC2-10 modellari kiradi. Har ikkala modelda ham birinchi darajali o'tkazgich yoki sim orqali transformator teshigiga o'tadi, shu bilan birga, kesilgan o'rnatish oyoqlari qo'shimcha o'rnatish yig'ilmasiga o'rnatishni qo'llab-quvvatlaydi. Bu o'tkazuvchi yadrali tartib muhandislarga o'lchov va himoya sxemalari uchun aniq mexanik interfeys beradi, lekin mahsulotni tizim darajasidagi loyihalash yoki ishga qo'yishni tekshirishning o'rnini bosuvchi sifatida taqdim etmaydi.

Loyiha jamoasi uchun birinchi savol faqatgina hozirgi o'tkazgich transformatorining kuchlanish sinfi 10 kV ekanligini tekshirish emas. Aksincha, qandaydir bor (tirqish), birinchi tok diapazoni, ikkinchi tok varianti, aniqlik sinfi, o'rnatish maydoni va himoya sxemasi haqiqiy kubikulaga mos kelishini aniqlash muhimroqdir. LMZC(2,3)-10 o'tkazgichli, yopiq, qovurilgan rezinadan yasalgan tok transformatori shu talablarga mos keladigan hujjatlashtirilgan variantlarni taqdim etadi. Yakuniy tanlov va rele sozlamalari loyiha spetsifikatsiyasiga va amal qilayotgan mahalliy talablarga mos ravishda malakali elektr muhandislari tomonidan tasdiqlanishi kerak.

Asosiy texnik xarakteristika

Parametr Mavjud spetsifikatsiya
Seriyalar va modellar LMZC(2,3)-10; LMZC3-10 va LMZC2-10
Qurilish O'tkazgichli, yopiq, qovurilgan rezinadan yasalgan (quyish turidagi)
Nominal kuchlanish sinfi 10 kV
Baho qilinayotgan asosiy to'kimagacha 50 / 75 / 100 / 150 / 200 / 300 / 400 / 500 / 600 A
Nominal ikkinchi darajali tok 5 A yoki 1 A
Nominal chastota 50 Gs yoki 60 Gs
O'lchash aniqligi sinflari 0.2s / 0.2 / 0.5
Himoya aniqligi sinflari 10P15 / 10P10 / 10P5
Mahsulot standarti GB20840.1 va GB20840.2

Ko'rsatilgan texnik shartlar yukning quvvat omilini cos φ = 0,8 ortga qolish, ifloslanish darajasi II, atrof-muhit harorati −15 °C dan +40 °C gacha (sutkalik o'rtacha harorat 30 °C dan oshmasligi kerak) va dengiz sathidan balandlik 1000 m gacha ni o'z ichiga oladi. Bu shartlar barcha muhitlarga umumiy ruxsat emas, balki belgilangan ishlatish shartlaridir. Agar loyihada boshqa atrof-muhit, balandlik, masofa yoki tizim shartlari bo'lsa, javobgar muhandislik jamoasi xarid qilishdan oldin mosligini tekshirib chiqishi kerak.

Namuna farqlari va tanlash mantiqasi

LMZC3-10 o'lchash va himoya qilish uchun mo'ljallangan tok transformatorlarining funksiyalarini birlashtiradi. Uning nominal ichki diametri 82 mm, tashqi diametri esa 130 mm. LMZC2-10 ikkita g'altak guruhini qo'shadi va 45 mm nominal ichki diametrli, 102 mm tashqi diametrli konstruktsiyaga ega. LMZC2-10 uchun keltirilgan ikkita g'altak aniqlik variantlari: 0.25, 0.5, 10P10 va 10P5. Shuning uchun tanlov o'tkaziladigan o'tkazgichning o'lchami, g'altaklar soni va mavjud elektr ta'minot qurilmalari joylashuviga mos keladigan joy hajmi orasidagi muhandislik solishtirishiga asoslanadi; bu biror modelning umumiy ma'noda yaxshiroq ekanligini tasdiqlash emas.

  • O'rnatilgan birinchi darajali o'tkazgich: birinchi darajali o'tkazgich yoki sim kabeli ichki diametrdan o'tadi.
  • Yopiq, qovurilgan rezin konstruksiyasi: mahsulot berilgan elektr ta'minot qurilmalari vazifasiga mos ravishda yopiq, quyish usulida ishlab chiqarilgan transformator sifatida tasvirlangan.
  • O'lchash variantlari: 0.2s, 0.2 va 0.5 o'lchash sinflari keltirilgan.
  • Himoya variantlari: 10P15, 10P10 va 10P5 himoya sinflari keltirilgan.
  • O'rnatish interfeysi: kesilgan oyoqlar rasmiy o'rnatish usulini ta'minlaydi.

Ma'lumotlar varaqasi mos kelishi faqat boshlanishdir. 50–600 A birinchi oqim doirasi va 5 A yoki 1 A ikkinchi oqim variantlari faqat ulangan hisoblagich, rele, yuk, o'tkazgich va himoya koordinatsiyasi talablari birgalikda tekshirilgandan keyingina foydali bo'ladi. Ayniqsa, tok transformatorini alohida tanlash to'liq himoya sxemasini ta'minlamaydi, shuning uchun ulangan tizimning bir qismi sifatida himoya releni turlari va ularning sozlamalari ham ko'rib chiqilishi kerak.

O'lchamlar va o'rnatish jihatlariga e'tibor berish

O'lchov LMZC3-10 LMZC2-10
Nominal Bore Diametr 82 mm 45 мм
Tashqi diametr 130 mm 102 mm
Asosdan yuqorigi teshik markazining balandligi 90 mm 77 mm
O'rnatish slotlari orasidagi masofa 95 mm 100 mm
O'rnatish slotining uzunligi 15 mm 15 mm
Korpusning chuqurligi 40 mm 80 mm
lmzc2-3-10-dimensions-02.webplmzc2-3-10-dimensions-01.webp

Fizikaviy moslik elektr darajasi kabi e’tibor talab qiladi. Siqilgan 33 kV avtomatik uzluksizlik qurilmasi paneli yoki 10 kV qopqoq kabelga ulanish, egilish radiusi, terminalga kirish va texnik xizmat ko’rsatish uchun yetarli joy kabi cheklovlar qo’yishi mumkin, bu esa faqat nominal ichki diametrni solishtirish bilan hal etilmaydi. Chizma yoki sotib olish buyurtmasini berishdan oldin o’tkazgich yo’nalishini, o’rnatish oyoqlari orasidagi masofani, chuqurligini va kirish imkoniyatini tasdiqlang. Bu ayniqsa transformator mavjud kubikulaga o’rnatiladigan hollarda muhimdir.

Qo'llanilishi

LMZC(2,3)-10 o’tkazgich orqali o’tadigan qoplangan rezin tok transformatori gaz izolyatsiyali avtomatik uzluksizlik qurilmalari va siqilgan 10 kV tarqatish avtomatik uzluksizlik qurilmalari uchun ikkilamchi hisoblash va himoya tarmoqlari uchun mo’ljallangan. Ushbu transformator quyidagi holatlarda baholanishi mumkin: 0.2s, 0.2 yoki 0.5 aniqlik sinflari talab qilinadigan hisoblash tarmoqlari; 10P15, 10P10 yoki 10P5 xarakteristikasi talab qilinadigan himoya rele tarmoqlari; shuningdek, birinchi darajali o’tkazgich o’rtasidan o’tadigan yangi yoki qayta jihozlangan kubikulalar.

LMZC2-10 ning ikki g‘altakli tartibi kerak bo‘lganda, muhandislar ro‘yxatdagi g‘altak sinflarini loyihaning alohida o‘lchov va himoya vazifalariga solishtirishlari mumkin. Har bir qo‘llanilish uchun yuk, nisbat, aniqlik sinfi, izolyatsiya mosligi, terminal ulanishlari va himoya sozlamalari to‘liq tizim loyihasiga mosligini tekshiring. Chaqmoq impulsi testi yoki boshqa belgilangan test talablari aniq loyiha doirasiga va qo‘llaniladigan standart nashriga mosligi tasdiqlanishi kerak; bu faqat seriyaviy belgilashdan kelib chiqmaydi.

Taqsimot tizimi loyihasi nuqtai nazaridan, LMZC(2,3)-10 O‘tishli yadrali qo‘yilma rezinaviy tok transformatori o‘tkazgich yo‘nalishi, ikkilamchi zanjir yuklanishi, korpusdan bo‘sh joy va rele koordinatsiyasi talablari bilan solishtirilishi kerak, shundan keyingina yakuniy tasdiqlanadi.

Amaliy sotib olish nazorat ro‘yxati

  1. Mavjud 50–600 A qadamdan kerakli birinchi tokni aniqlang.
  2. Ikkinchi zanjir 5 A yoki 1 A talab qilishini tasdiqlang.
  3. Loyiha tomonidan talab qilinadigan o'lchov, himoya yoki ikki g'ildirakli aniqlik konfiguratsiyasini tanlang.
  4. Kubikulaning joylashuv chizmasiga mos ravishda teshik diametri, tashqi diametr, o'rnatish slotlari, korpus chuqurligi va o'tkazgich yo'nalishini tekshiring.
  5. Atmosferaviy chegaralar, qo'llaniladigan standartlar va loyiha uchun talab qilinadigan sinov hujjatlari bilan tanishib chiqing.
  6. Energiya berishdan oldin tok transformatorining ma'lumotlarini hisoblagich, rele va elektr ta'minot uskunalari himoya tadqiqoti bilan muvofiqlashtiring.

Ta'min etilgan mahsulot ma'lumotlaridagi tijorat shartlari minimal buyurtma miqdori (MOQ) 1 dona, T/T to'lov shakli va to'lov qabul qilgandan keyin 20 kun ichida yetkazib berilishini ko'rsatadi. Mavjudlik, texnik konfiguratsiya, hujjatlar va yetkazib berish aniq buyurtma uchun qaytadan tasdiqlanishi kerak. Loyihaga xos texnik taklif va narx taklifini olish uchun talab qilinadigan nisbat, ikkilamchi tok, aniqlik darajasi, yuk, o'lchamlar va qo'llanish haqida batafsil ma'lumotni yetkazib beruvchi kompaniyaga murojaat qiling.

LMZC(2,3)-10 O'tkazuvchi yadrali qoplamali rezinaviy tok transformatori, 10 kV, yopiq tur, gaz izolyatsiyali uloqtirgichlar uchun

Nominal birinchi 50-600 A, ikkinchi 5 A yoki 1 A, o'lchash sinfi 0.2s/0.2/0.5, himoya sinfi 10P15/10P10/10P5, ikkita chulg'am

So'rov yuborish

Xususiy mahsulotlar

Bepul taklif oling

Bizning vakilimiz tez orada siz bilan bog'lanadi.
Email
Ism
Kompaniya nomi
Message
0/1000