hxgn15-12-high-voltage-ring-main-unit-rmu, hxgn15-12-high-voltage-ring-main-unit-rmu, /hxgn15-12-ring-main-unit
Inquiry
Inquiry

HXGN15-12 High-Voltage Ring Main Unit (RMU)

11kV/12kV
Air-Insulated Switchgear (AIS) Equipped with SF6 Load Break Switches and VS1 Vacuum Circuit Breakers (VCB)Fully customizable high/low-voltage switchgear engineered to your exact specifications and site requirements — CE certified, 10-year warranty.

Request a Quote
  • Overview

Overview

HXGN15-12 High-Voltage Ring Main Unit (RMU) Overview

The HXGN15-12 High-Voltage Ring Main Unit (RMU) is a compact 12 kV distribution switchgear assembly for secondary distribution networks. The supplied product material describes an SF6-insulated design that combines load-break switching, transformer-feeder protection options, and busbar interconnection within a compact cabinet arrangement. For a project team, the value of an RMU is not simply that it fits a given voltage class. It is that the switching arrangement, cable configuration, protection scheme, and site constraints can be evaluated together before the equipment is specified.

Documented Electrical Ratings

The existing product information identifies a rated voltage of 12 kV and a main-bus rated current of 630 A. It also lists a rated short-circuit making current of 50 kA peak, a rated short-time withstand current of 20 kA for 3 seconds, and a rated transfer current of 1600 A for the switch-fuse arrangement. These values are supplied as product facts, but final selection should still be confirmed against the project fault-level study, protection-coordination study, and the required utility or local-grid documentation.

Serial No.

Name

Unit

Value

1

Rated Voltage

kV

12

2

Rated Frequency

Hz

50

3

Main Bus Rated Current / Maximum Rated Current of Fuse

A

630, 125

4

Rated Short-time Withstand Current of Main Circuit and Grounding Circuit

kA/S

20, 3

5

Rated Peak Withstand Current of Main Circuit and Grounding Circuit

kA

50

6

Rated short-circuit Making of Circuit and Grounding Circuit

kA

50

7

Full-capacity Breaking Times of Load Switch

times

100

8

Breaking Current of Fuse

kA

31.5, 40

9

Rated Closed-loop Breaking Current

A

630

10

Rated Transfer Current

A

1600

11

Mechanical Life

times

2000

12

Ligin Power Frequency Withstand Voltage (Peak) Relative to Ground / Isolation Fracture

kV

42, 48

13

Lightting Impulse Withstand Voltage Voltage of Ssolation Fracture

kV

75, 85

14

1 min Power Frequency Withstand Voltage of Secondary Circuit

kV

2

15

Protection Class

IP3X

Overall Dimensions

Size

Application Range

Hight H(mm)

1400

Suitable for single-core cables

1600

Suitable for single-core cables

1800

Suitable for three-core cables

Width W(mm)

375

Incoming and outgoing lines

500

750

Depth D(mm)

918

The HXGN15-12 High-Voltage Ring Main Unit (RMU) documentation references IEC 62271-200 and GB 3906. Standards references are useful procurement checkpoints, rather than substitutes for a project-specific review. Confirm the applicable edition, test clauses, certificate scope, and market-specific requirements with the supplier and the relevant authority before final specification.

Sealed Insulation and Switching Functions

The supplied description states that the high-voltage components are enclosed in a hermetically sealed stainless-steel SF6 tank. It describes factory-filled, sealed-for-life construction intended to limit moisture and dust ingress in demanding locations such as humid or underground installations. The stated dielectric values are 42 kV / 48 kV power-frequency withstand and 75 kV / 85 kV lightning-impulse withstand, each expressed for the listed to-ground and isolation-fracture conditions. The product material also states helium leak testing before dispatch and an IP3X protection class.

For a buyer comparing an air-insulated arrangement with an SF6-based sealed arrangement, neither option is universally better. A sealed approach may be attractive where environmental exposure, footprint, or maintenance access is a major concern; however, the right solution depends on site practice, applicable environmental obligations, maintenance policy, and the system configuration. Ask for the equipment-specific documentation rather than inferring performance from the insulation medium alone.

  • Compact integration of switching and feeder functions.
  • Documented 630 A main-bus rating for the stated 12 kV design.
  • SF6 sealed stainless-steel tank described in the supplied material.
  • Switch-fuse coordination information, including 1600 A transfer current.
  • Front-access operation and bottom cable entry stated for the cabinet range.

Protection Coordination and Layout Considerations

The 1600 A transfer-current value is particularly relevant where a switch-fuse transformer feeder is being considered. It relates to coordination between the load-break switch and current-limiting fuse in intermediate-fault conditions. The final protection arrangement should be checked against the selected transformer, fuse curve, relay settings, fault-current range, and network operating philosophy. If downstream relay protection is included, obtain the required coordination documentation for the complete scheme.

Projects that seem straightforward on paper can face delays when the HXGN15-12 High-Voltage Ring Main Unit (RMU) arrives and the cable-entry configuration does not match the conduit arrangement assumed during civil planning. The product material states removable bottom gland plates and front-access operation. Confirm cable direction, gland-plate dimensions, bending radius, termination type, and the selected cable construction before locking the cabinet layout. This is often more useful than treating cabinet width as the only installation constraint.

Dimensions and Cable Options

The documented module width is 375 mm for certain incoming and outgoing functions, with 500 mm and 750 mm width options also listed. Cabinet depth is stated as 918 mm. The product description lists 1400 mm and 1600 mm heights for single-core cable arrangements and 1800 mm for three-core cable arrangements. These dimensions can support early space planning, but the final footprint must be based on the selected functional lineup, safe working clearances, cable-bending requirements, and local installation rules.

Suitable Project Contexts

Urban and Underground Distribution

The compact form factor and sealed insulation described for the HXGN15-12 High-Voltage Ring Main Unit (RMU) can be considered for urban distribution locations where available space and environmental exposure need careful review. The final choice should consider ventilation, access, flood risk, local safety rules, and the cable system.

Industrial and Commercial Incoming Supply

For an industrial plant or commercial facility supplied from a medium-voltage ring network, the RMU can serve as a switching and isolation point when its configuration and ratings suit the network study. Procurement teams should align engineering, operations, finance, and compliance reviewers around the same approved specification.

Renewable-Energy Collection Systems

Where a collector substation needs compact medium-voltage switching, evaluate the RMU within the whole collection-system design. Do not use unrelated claims such as amorphous core transformer advantages as a product feature of this switchgear; those are transformer-specific considerations.

Procurement and Verification Checklist

The supplied commercial information states ISO 9001 manufacturing, MOQ of one set, an indicative delivery of 20–35 working days, supply capacity of 300 sets per month, FOB Ningbo or Shanghai, and T/T or L/C at sight. These are supplier-provided terms that should be reconfirmed in the quotation and contract. The product material also lists factory tests including leak testing, dielectric tests, circuit resistance, switch timing, interlock function, and listed current-related tests.

Before purchase, request the final single-line diagram, general arrangement drawing, routine-test scope, type-test evidence where required, certificate scope, cable interface details, operating mechanism details, and shipping schedule. An outdoor termination kit is a separate interface item unless it is explicitly included in the approved offer. Anyway, the key point is not to assume a standard arrangement fits every site: use the documented ratings as a starting point, then confirm the configuration against the actual network and installation conditions.

Product Images

a81afe91ff0d21854e9c8de94712553a.jpgd70a05c77e2bbf0c1c9b9d9bcee49908.jpgeddea63b95e4205369bccc1218501b05.jpge42887415e97d14bf0e7116c8c8aa00c.jpg

FAQ

1. What is HXGN15-12 ring main unit used for?

HXGN15-12 is indoor fixed metal-enclosed ring main unit for 12kV medium voltage distribution network.It realizes ring network power supply, power segmentation and feeder protection, widely used in urbandistribution networks, residential districts and box substations.

2. What structural characteristics does HXGN15-12 have?

It adopts fixed cabinet structure with simple and reliable layout. The cabinet is divided into independentfunctional compartments. The main switch is fixed-mounted, with clear visible isolation gap to guaranteesafety during maintenance operation.

3. What core technical parameters of HXGN15-12 can be customized?

We can customize rated current, short-circuit withstand current and main circuit combination scheme.Different circuit configurations can be designed to meet ring-in, ring-out and transformer feederrequirements.

4. What certifications do your HXGN15-12 ring main units have?

All our HXGN15-12 ring main units hold CE certification. We can provide CE documents and complete technical datasheets for tender submission and customs clearance.

5. What warranty support can you provide for HXGN15-12?

We provide 10 years warranty for all HXGN15-12 ring main units. Our technical team offers remote operation guidance and fault analysis during the whole warranty period.

HXGN15-12 High-Voltage Ring Main Unit (RMU)

11kV/12kV
Air-Insulated Switchgear (AIS) Equipped with SF6 Load Break Switches and VS1 Vacuum Circuit Breakers (VCB)Fully customizable high/low-voltage switchgear engineered to your exact specifications and site requirements — CE certified, 10-year warranty.

Request a Quote

Featured Products

hxgn15 12 high voltage ring main unit rmu-1

Get a Free Quote

Our representative will contact you soon.
Email
Name
Company Name
Message
0/1000