zw32-outdoor-high-voltage-vacuum-circuit-breaker, zw32-outdoor-high-voltage-vacuum-circuit-breaker, /zw32-series
EN
10kV/12kV/24kV/40.5kV
Intelligent Overhead-Mounted Boundary VCB with Disconnector
Self-developed mechanism structure with high-grade internal components for reliable switching in power distribution — CE certified, 10-year warranty.
The ZW32 Outdoor HV Vacuum Circuit Breaker 10KV 12KV 24KV 40.5KV Intelligent Watching With Disconnector Pole Mounted Boundary VCB from JYDQ is a unified three-voltage-class platform designed for overhead distribution and sub-transmission protection. This outdoor HV vacuum circuit breaker uses a vacuum interrupter with a motor-driven stored-energy spring mechanism accepting AC/DC 220V, 110V, and DC 24V control voltages. From a distribution system design perspective, the ZW32 Outdoor HV Vacuum Circuit Breaker addresses protection grade, multi-voltage compatibility, and fleet standardisation in one IEC 62271-100 and GB 1984 certified product family.
| Place of Origin | Zhejiang, China |
| Brand Name | JYDQ |
| Model Number | ZW32-12 / ZW32-24 / ZW32-40.5 |
| Certification | ISO 9001, IEC 62271-100, GB 1984 |
| Voltage Classes | 12kV / 24kV / 40.5kV |
| Rated Current (max) | 1250A (12/24kV) / 1600A (40.5kV) |
| Rated Breaking Current (max) | 20kA (12kV) / 31.5kA (24kV) / 31.5kA (40.5kV) |
| Installation | Outdoor pole-mounted, three-phase common-frame |
| Interruption Medium | Vacuum interrupter |
| Mechanical Life | 10,000 operations |



| MOQ | 1 Set |
| Price | FOB Ningbo/Shanghai, on request |
| Packaging | Export-standard wooden crate |
| Delivery | 15–30 working days |
| Payment | T/T, L/C at sight |
| Supply Ability | 500 Sets per Month |
The ZW32 Outdoor HV Vacuum Circuit Breaker With Disconnector Pole Mounted is available in six configurations: dual power manual switching, dual power automatic transfer, integrated primary/secondary without disconnector, integrated primary/secondary with disconnector, intelligent watching without isolating switch, and intelligent watching with isolating switch (Boundary VCB).






The ZW32 Outdoor HV Vacuum Circuit Breaker 10KV 12KV 24KV 40.5KV series delivers a unified pole-mounted platform. Unlike maintaining separate product families per voltage level, this outdoor HV vacuum circuit breaker with disconnector shares a common mechanism, spare parts inventory, and FTU interface specification — an approach that reduces lifecycle procurement and maintenance complexity for utilities operating multi-voltage overhead networks. With a rated breaking capacity of 20kA at 12kV and 31.5kA at both 24kV and 40.5kV, continuous current of up to 1600A, and an opening time of 18–45ms among the fastest in the outdoor pole-mounted class, the ZW32 Boundary VCB is engineered for dependable fault interruption at distribution and sub-transmission voltage levels.
The ZW32 Outdoor HV Vacuum Circuit Breaker Intelligent Watching With Disconnector variant integrates directly with FTU/RTU distribution automation systems. The motor-driven stored-energy spring mechanism accepts AC/DC 220V, 110V, and DC 24V control voltages — enabling direct integration with any substation auxiliary supply architecture without interposing converters. The ZW32-40.5 variant supports dual-frequency 50/60Hz operation, making the ZW32 Outdoor HV Vacuum Circuit Breaker Pole Mounted suitable for export to 60Hz markets including the Americas, Middle East, and Southeast Asia without requiring frequency-specific variant sourcing.
| Parameter | Unit | ZW32-12 | ZW32-24 | ZW32-40.5 |
|---|---|---|---|---|
| Rated Voltage | kV | 12 | 24 | 40.5 |
| Rated Frequency | Hz | 50 | 50 | 50/60 |
| Rated Current | A | 630/1250 | 630/1250 | 1250/1600 |
| SC Breaking Current | kA | 20 | 20/25/31.5 | 25/31.5 |
| Peak Withstand Current | kA | 50 | 50/63/80 | 63/80 |
| Mechanical Life | operations | 10,000 | 10,000 | 10,000 |
| SC Breaking Times | times | 30 | 30 | 30 |
| LI Withstand (Phase-Gnd) | kV | 75 | 125 | 185 |
| Opening Time | ms | 18–45 | 18–45 | — |
| Main Circuit Resistance | μΩ | ≤100 | ≤100 | ≤100 |
The ZW32 Outdoor HV Vacuum Circuit Breaker Pole Mounted serves as the primary protection device for 12kV distribution, 24kV sub-transmission, and 40.5kV sub-transmission overhead feeders. In experience, engineers specifying outdoor vacuum circuit breakers often underestimate system integration challenges: choosing a pole-mounted boundary VCB in isolation is straightforward, but ensuring it integrates correctly with the upstream relay, downstream reclosers, and the distribution automation master station is where unit protection system coordination issues typically appear. The ZW32 With Disconnector addresses this with a common FTU interface specification across all three voltage classes and a multi-voltage mechanism that eliminates auxiliary power supply constraints. During commissioning and scheduled maintenance on ZW32-equipped poles, site teams must apply an appropriately rated earthing stick before any physical contact with conductors; the built-in mechanical position indicator and non-resettable operation counter assist in confirming open/closed status prior to earthing stick application.
For 40.5kV sub-transmission feeders, the ZW32 Outdoor HV Vacuum Circuit Breaker With Disconnector supports the O-0.1s-CO-3s-CO-6s-CO-60s auto-reclose sequence with a 0.1-second first dead time, enabling rapid supply restoration following transient overhead line faults. The 50/60Hz dual-frequency rating of the ZW32-40.5 confirms its suitability for both standard 50Hz networks and 60Hz export markets in the Americas and Middle East.
You will see suppliers position outdoor vacuum circuit breakers as either voltage-class-specific for maximum technical optimisation, or platform-unified for standardisation benefits. Both framings are partially true — but for a utility operating at 12kV, 24kV, and 40.5kV, maintaining three separate breaker families means three training programmes, three spare parts inventories, and three FTU interface specifications. The ZW32 Outdoor HV Vacuum Circuit Breaker 10KV 12KV 24KV 40.5KV Intelligent Watching With Disconnector Pole Mounted Boundary VCB resolves this by delivering class-appropriate insulation ratings and breaking capacities within a single certified platform — backed by IEC 62271-100 type-test evidence and JYDQ ISO 9001 quality management.
In experience, the parameter most frequently underweighted in outdoor HV vacuum circuit breaker specification is control voltage compatibility. Engineers often discover late in a project that the substation DC bus standard does not match the breaker coil rating, requiring interposing relays that add cost and failure risk. The ZW32 Outdoor HV Vacuum Circuit Breaker With Disconnector addresses this directly with its AC/DC 220V/110V/DC 24V multi-voltage mechanism design across the complete 10KV 12KV 24KV 40.5KV voltage range.




1. What is the core working principle of your vacuum circuit breaker?
The vacuum circuit breaker uses high vacuum inside the interrupter chamber to extinguish electric arc.There is almost no gas medium inside the sealed vacuum tube, which can quickly cool and cut off the arcwhen the circuit is disconnected. This design brings low contact wear, stable breaking performance andlong mechanical life.
2. What types of vacuum circuit breakers can you provide?
We supply indoor fixed type, indoor withdrawable type, outdoor pole-mounted type and outdoor boxtype vacuum circuit breakers. Different models are suitable for cabinet installation, overhead line,distribution substation and industrial power system protection.
3. What are the main technical parameters we can customize?
We can customize rated current, short-circuit breaking current, mechanical operation cycle and auxiliary contact quantity. We can also adjust the voltage coil of operating mechanism to match local control power supply standard.
4. What certifications do your vacuum circuit breakers have?
All vacuum circuit breakers from our factory hold CE certification. We can supply CE test documents and complete technical datasheets for tender review and customs clearance.
5. What is your warranty coverage for vacuum circuit breakers?
We offer 10 years warranty for all vacuum circuit breakers. Our technical team provides remotetroubleshooting and operation guidance during the whole warranty period to guarantee stableequipment operation.
10kV/12kV/24kV/40.5kV
Intelligent Overhead-Mounted Boundary VCB with Disconnector
Self-developed mechanism structure with high-grade internal components for reliable switching in power distribution — CE certified, 10-year warranty.