Customizable
40.5kV / 35kV / 30kV
Indoor withdrawable armored metal-clad switchgear
Fully customizable high/low-voltage switchgear engineered to your exact specifications and site requirements — CE certified, 10-year warranty.
The KYN61-40.5 High Voltage Switchgear Customizable 40.5kV 35kV 30kV Indoor Withdrawable Armored Metal-clad Power Distribution Cabinet is an indoor metal-clad armored withdrawable AC switchgear platform engineered for primary substations, power plants, and demanding industrial installations. From a distribution system design perspective, selecting the right 40.5 kV switchgear is a balancing act between personnel safety, fault interruption performance, and long-term maintenance economics. At 40.5 kV, available arc energy during an internal fault is approximately three times that at 12 kV, making armored construction a fundamental safety requirement. JYDQ manufactures every panel under ISO 9001 quality management with complete type-test certification to IEC 62271-200 and GB 3906 at KEMA-accredited independent laboratories.
The metal-clad armored architecture of the KYN61-40.5 High Voltage Switchgear Customizable 40.5kV 35kV 30kV Indoor Withdrawable Armored Metal-clad Power Distribution Cabinet employs four fully segregated compartments—busbar, circuit breaker, cable termination, and low-voltage control—each isolated by grounded metal partitions. Pressure-relief flaps on each compartment vent arc gases safely away from switchroom personnel. The circuit breaker compartment door incorporates mechanical interlocks with the handcart racking mechanism: the door cannot be opened unless the breaker is in the isolated position. You will encounter 40.5 kV switchgear positioned either as a commodity item or as a system safety component—both framings are partially true, but neither is complete without knowing the fault level and switching duty of your application.
The switchgear accommodates ZN85-40.5 vacuum circuit breakers rated 1250 A to 2000 A with breaking capacities of 20 kA, 25 kA, and 31.5 kA. The circuit breaker achieves M2-class mechanical endurance of 100,000 close-open operations—ten times the 10,000-operation industry threshold—eliminating mechanism overhaul from the lifecycle maintenance plan for capacitor bank switching, automatic load transfer, and auto-reclose applications. Operating time is specified as a defined range: 30–60 ms for opening and 50–100 ms for closing, giving protection engineers the precise timing data required for coordination calculations. The 230 W energy storage motor completes a full spring charge in 12 seconds or less, supporting the O-0.3s-CO-180s-CO operating sequence. Coils accept DC 220 V/110 V or AC 220 V/110 V, with opening coil currents of 0.96 A at 220 V and 1.05 A at 110 V.




KYN61-40.5 panels serve as the main switchboard in utility primary substations, supplying outgoing feeders at the critical 40.5 kV/12 kV transformation level. The 2000 A / 31.5 kA / 80 kA peak configuration supports bus-tie positions in double-busbar substations. If your site altitude exceeds 1000 m, altitude correction is available and should be confirmed at specification stage—standard ratings apply below 1000 m and may require adjustment at higher elevations.
With 2000 A / 31.5 kA capability, the KYN61-40.5 High Voltage Switchgear Customizable 40.5kV 35kV 30kV Indoor Withdrawable Armored Metal-clad Power Distribution Cabinet provides medium-voltage auxiliary power for power plant balance-of-plant equipment and heavy industrial processes including steel mill arc furnace switching and chemical plant distribution. Projects have encountered cable entry delays when termination space requirements did not match the civil conduit layout—verifying 40.5 kV cable bending radius requirements against the civil arrangement at specification stage avoids field modifications that affect cost and schedule.
Name |
|
Unit |
Parameter |
Rated Operating Voltage |
Opening Coil |
V |
DC220/110 AC220/110 |
Closing Coil | |||
Rated Operating Current |
Opening Coil |
A |
0.96(220 V) 1.05(110V) |
Closing Coil | |||
Energy Storage Motor Power |
|
W |
230 |
Rated Voltage of Energy Storage Motor |
|
V |
DC220/110 AC220/110 |
Energy Storage Time |
|
S |
≤ 12 |
Serial Number |
Name |
Unit |
Parameter |
1 |
Rated Voltage |
kV |
40.5 |
2 |
Rated Current |
A |
1250 1600 2000 |
3 |
Rated Frequency |
Hz |
50 |
4 |
Rated Short-time Withstand Current |
kA |
20 25 31.5 |
5 |
Rated Peak Withstand Current |
kA |
50 63 80 |
6 |
Rated Peak Withstand Current |
kV |
95/1min |
7 |
Rated Lightning Impulse Withstand Voltage |
kV |
185 |
8 |
Rated Short-circuit Duration |
s |
4 |
9 |
Protection Class |
|
IP3X |
Serial No. |
Name |
Unit |
Parameter |
1 |
Rated Voltage |
kV |
40.5 |
2 |
Rated Frequency |
Hz |
50 |
3 |
Rated Power Frequency Withstand Voltage |
kV |
95/1min |
4 |
Rated Lighting Impulse Withstand Voltage |
kV |
185 |
5 |
Rated Current |
A |
1250 1600 2000 |
6 |
Rated Short-time Withstand Current |
kA |
20 25 31.5 |
7 |
Rated Short-circuit Breaking Current |
kA |
20 25 31.5 |
8 |
Rated Peak Withstand Current |
kA |
50 63 80 |
9 |
Rated Short-circuit Duration |
ms |
4 |
10 |
Opening Time |
ms |
30 ≤ t ≤ 60 |
11 |
Closing Time |
ms |
50 ≤ t ≤ 100 |
12 |
Rated Short-circuit Breaking Current Times |
times |
20 |
13 |
Mechanical Life |
times |
100000 |
For procurement teams evaluating multiple 40.5 kV switchgear suppliers, confirm the type test scope covers power-frequency withstand (95 kV / 1 min), lightning impulse (185 kV), short-circuit breaking, short-time withstand (31.5 kA / 4 s), peak withstand (80 kA), IP3X verification, internal arc classification, and mechanical endurance at 100,000 operations. For buyers without in-house HV engineering expertise, supplying your one-line diagram, available fault level data, load current profile, and auxiliary supply voltage enables JYDQ to determine the correct configuration for your project without overspecification.
1. What is KYN61-40.5 high voltage switchgear mainly used for?
KYN61-40.5 is indoor metal-clad withdrawable high voltage switchgear for 40.5kV power system. Itundertakes power receiving, distribution and fault protection in power substations, renewable energybooster stations and large industrial power supply systems.
2. What structural characteristics does KYN61-40.5 have?
The cabinet adopts metal partition structure and is divided into multiple independent sealedcompartments. The main switch is withdrawable handcart type. It can realize physical isolation from themain circuit, ensuring high safety during maintenance work.
3. What certifications do your KYN61-40.5 switchgears have?
All KYN61-40.5 high voltage switchgears from our factory hold CE certification. We can provide CE documents and full technical datasheets for tender review and customs clearance.
4. What warranty support can you provide for KYN61-40.5?
We provide 10 years warranty for all KYN61-40.5 switchgears. Our technical team provides remote operation guidance and fault analysis throughout the warranty period.
Customizable
40.5kV / 35kV / 30kV
Indoor withdrawable armored metal-clad switchgear
Fully customizable high/low-voltage switchgear engineered to your exact specifications and site requirements — CE certified, 10-year warranty.