Customizable
12kV/24kV
Indoor Gas-Insulated, Fully Insulated, Metal-Enclosed Switchgear (Ring Main Unit)
Fully customizable high/low-voltage switchgear engineered to your exact specifications and site requirements — CE certified, 10-year warranty.
The RM6 Ring Main Unit Customizable 12kV 24kV Indoor Gas Insulated Fully Insulated Metal-enclosed Power Distribution Cabinet RMU from JYDQ is a modular, SF6 gas-insulated switchgear platform for indoor medium-voltage distribution, certified to ISO 9001, IEC 62271-200, and GB 3906. Manufactured in Zhejiang, China, the RM6 Ring Main Unit Customizable 12kV 24kV Indoor Gas Insulated Fully Insulated Metal-enclosed Power Distribution Cabinet RMU addresses the complete functional range of a medium-voltage substation through nine configurable module types—C, F, V, CB, SL, M, D, PT, and +—within a single, mechanically integrated enclosure. From a distribution system design perspective, selecting the RM6 Ring Main Unit Customizable 12kV 24kV Indoor Gas Insulated Fully Insulated Metal-enclosed Power Distribution Cabinet RMU is a balancing act between fault protection requirements, switching duty, and future network growth.

The RM6 Ring Main Unit Customizable 12kV 24kV Indoor Gas Insulated Fully Insulated Metal-enclosed Power Distribution Cabinet RMU uses SF6 gas as the insulating and arc-quenching medium throughout its busbar and switching compartments. The SF6 volume is factory-sealed for the equipment's operational life—no site gas handling or recovery is required during normal service. The dielectric specification of the RM6 Ring Main Unit Customizable 12kV 24kV Indoor Gas Insulated Fully Insulated Metal-enclosed Power Distribution Cabinet RMU is consistent across all nine module types: 42/48 kV power-frequency withstand voltage and 75/85 kV lightning impulse withstand voltage, at 50 Hz. This applies to both 12 kV and 24 kV applications. If your project requires 24 kV nominal system voltage, the sealed SF6 gas volume of the RM6 Ring Main Unit Customizable 12kV 24kV Indoor Gas Insulated Fully Insulated Metal-enclosed Power Distribution Cabinet RMU covers both voltage classes. The SF6-insulated busbar enables compact indoor substation rooms where modular substation design eliminates the air-clearance requirements of conventional metal-enclosed switchgear.

Unit Code |
Meaning |
Unit Code |
Meaning |
C |
Standard single-bushing load switch unit |
- |
Bus-side bushing |
F |
Load switch-fuse combination electrical unit |
SL |
Bus tie unit |
V |
Circuit breaker unit |
M |
Metering unit |
D |
Cable incoming unit (without switch) |
PT |
PT unit |
+ |
Metering unit |
1K2(4) |
Load switch unit with double bushings |
Model |
|
C Module |
F Module |
V Module |
V Module |
CB Module |
CB Module |
|
|
Composite Switch |
Combined Apparatus |
Vaccum Switch |
V Module Isolation/ Earthing Switch |
CB Module Vacuum Circuit Breaker |
CB Module Isolation/ Earthing Switch |
Rated Voltage |
kV |
12 |
12 |
12 |
12 |
12 |
12 |
Rated Frequency |
Hz |
50 |
50 |
50 |
50 |
50 |
50 |
Power Frequency Withstand Voltage (Phase-to-Phase/Port) |
kV |
42/48 |
42/48 |
42/48 |
42/48 |
42/48 |
42/48 |
Lightning Impulse Withstand Voltage |
kV |
75/85 |
75/85 |
75/85 |
75/85 |
75/85 |
75/85 |
Rated Current |
A |
630 |
注 1) |
630 |
|
1250/630 |
|
Rated Current |
A |
630 |
|
|
|
|
|
Rated Closed-LLoop Breaking Current (Peak) |
A |
135/135 |
|
|
|
|
|
Rated Cable Charging Breaking Current |
A |
50 |
80 |
|
|
|
|
Rated Peak Withstand Current |
kA |
50 |
|
|
|
|
|
Rated Short-Time Withstand Current |
kA/3s |
20 |
|
|
|
|
|
Rated Transfer Current |
kA |
|
31.5 |
20 |
|
25 |
|
Rated Transfer Current |
A |
|
1750 |
|
|
|
|
Max Current of Fused Disconnector |
A |
- |
125 |
|
|
|
|
Loop Resistance |
μΩ |
≤ 300 |
≤ 600 |
|
|
|
|
Times |
次 |
5000 |
3000 |
5000 |
2000 |
5000 |
5000 |
Note: 1) Depends on the current rating of the fuse
The RM6 Ring Main Unit Customizable 12kV 24kV Indoor Gas Insulated Fully Insulated Metal-enclosed Power Distribution Cabinet RMU module catalog covers all medium-voltage switching, protection, and metering functions:

Additional modules can be added to either end of an existing RM6 Ring Main Unit Customizable 12kV 24kV Indoor Gas Insulated Fully Insulated Metal-enclosed Power Distribution Cabinet RMU assembly at any point during the substation's operational life, via the factory-prepared SF6 busbar expansion interface—typically within a single shift, without field gas handling. You will see suppliers position fixed-configuration units as a lower-cost option; both framings are partially true, but when the distribution network evolves and additional feeders are required, the cost of replacing a fixed unit often exceeds the original cost of specifying the RM6 Ring Main Unit Customizable 12kV 24kV Indoor Gas Insulated Fully Insulated Metal-enclosed Power Distribution Cabinet RMU in a modular configuration.
For urban ring distribution networks, the RM6 Ring Main Unit Customizable 12kV 24kV Indoor Gas Insulated Fully Insulated Metal-enclosed Power Distribution Cabinet RMU provides C Module ring switching, F Module transformer protection, and SL Module bus sectionalizing for N-1 supply security. For industrial facilities, the CB Module's 5,000-operation endurance—a parameter most buyers underweight when comparing ring main unit options—suits high-fault-level networks with frequent switching duty. For EPC contractors procuring the RM6 Ring Main Unit Customizable 12kV 24kV Indoor Gas Insulated Fully Insulated Metal-enclosed Power Distribution Cabinet RMU across multiple markets, the IEC 62271-200 certification provides the documentation basis for grid authority pre-qualification. When an isolation transformer or other components must interface with the assembly, relay coordination between protection current transformer ratios and circuit breaker operating times should be reviewed at specification stage. Projects that have overlooked cable entry coordinate during civil design often encounter schedule delays when the arriving switchgear configuration does not match the buried conduit layout—confirming the factory cable entry arrangement before shipment reduces this risk.

The RM6 Ring Main Unit Customizable 12kV 24kV Indoor Gas Insulated Fully Insulated Metal-enclosed Power Distribution Cabinet RMU is certified to IEC 62271-200, ISO 9001, and GB 3906. When specifying medium-voltage switchgear subject to standards review, buyers should confirm the applicable IEC edition and local grid code requirements with the relevant authority before finalizing the specification. Buyers without in-house HV engineering expertise can access pre-sales application engineering support to confirm module configuration for their project. Supply terms: MOQ 1 Set; FOB Ningbo or Shanghai; delivery 25–40 working days; T/T or L/C at sight; supply capacity 300 Sets per month.
1. What is RM6 ring main unit used for?
RM6 is compact metal enclosed ring main unit for medium voltage distribution network. It is designed forring network power supply, realizing power loop closing and sectional control to improve power supplyreliability for urban distribution, residential area and industrial power system.
2. What structural features does RM6 ring main unit have?
The whole cabinet adopts sealed gas tank structure. The main switching components are enclosed inside the gas tank. The cabinet layout is compact, small footprint and suitable for installation in box substation and outdoor compact power station.
3. What key technical parameters of RM6 can be customized?
We can customize rated voltage, rated current and short-circuit withstand level. Different combinationschemes can be configured according to project requirements to meet ring-in, ring -out and transformerfeeder functions.
4. What certifications do your RM6 ring main units have?
All our RM6 ring main units hold CE certification. We can provide CE documents and complete technical datasheets for tender submission and customs clearance.
5. What warranty support can you provide for RM6 ring main unit?
We provide 10 years warranty for all RM6 ring main units. Our technical team offers remote operation guidance and fault diagnosis during the whole warranty period.